Setupsequence(continued) – Weidmuller UCVAR - Universal glavanically isolated signal converter Benutzerhandbuch
Seite 24

2
Enable/DisableAlarms
Alarms 1 & 2
Select
AL=Y
AL=n
Enable
Disable
Toggle
Accept
Note: alarm settings are only shown if they are enabled.
Alarmchannelone
Coil energisation
A1nE
A1nd
Normally energised
Normally de-energised
Toggle
Accept
Alarm type
A1=L
A1=H
Low type (active below setpoint)
High type (active above setpoint)
Toggle
Accept
Setpoint value
SP1=
50.0
Setpoint value
e.g., 50.0 %
-
Dec
-
Inc
Next
Accept
Deadband value
db1=
0.1
Deadband value
e.g., 0.1 %
-
Dec
-
Inc
Next
Accept
Timer delay
dL1=
20
Timer delay (set to 0 s to disable)
e.g., 20 s
-
Dec
-
Inc
Next
Accept
Alarmchanneltwo
Coil energisation
A2nE
A2nd
Normally energised
Normally de-energised
Toggle
Accept
Alarm type
A2=L
A2=H
Low type (active below setpoint)
High type (active above setpoint)
Toggle
Accept
Setpoint value
SP2=
50.0
Setpoint value
e.g., 50.0 %
-
Dec
-
Inc
Next
Accept
Deadband value
db2=
10.0
Deadband value
e.g., 10.0 %
-
Dec
-
Inc
Next
Accept
Timer delay
dL2=
20
Timer delay (set to 0 s to disable)
e.g., 20 s
-
Dec
-
Inc
Next
Accept
Generalalarmsettings
Alarm reset
sequence
nOr
rES
Automatic reset
Manual reset
Toggle
Accept
Setpoint
security
SECy
SECn
Setpoints fixed at setup
Can change setpoints
Toggle
Accept
SetupSequence(continued)