Weidmuller UPIT - Analog to frequency converter Benutzerhandbuch

Seite 20

Advertising
background image

20

Terminal

Signal

1

24 V DC (out)

Input signals

2

Current +

3

Common −

4

Voltage +

5

Not used

6

7

Link to change the set-up

Security Link

8

9

Neutral −

Power supply

10

Live +

11

Alarm Output

Alarm and Frequency Outputs

12

Frequency Pulse Output

13

Common

14

Not Used

15

16

Case

Earthing is via a stud on lower side of case

PulseandAlarmOutputs
The pulse and alarm outputs are Isolated Open Collector transistors
with a common negative return. They can be operated up to a
maximum frequency of 999.9 Hz. The outputs are rated to 200 mA
“on” state current or 0 V DC “off” state voltage and must be used with
back-emf diodes for inductive loads.
The mark/space ratio of the output pulse can be set to give an even or
a fixed (30 mS) pulse width.