3 reset – function – Baumer BA DABx AD2T Benutzerhandbuch
Seite 16

DABx_AD2T_BA_V1_0m.doc
16/20
Baumer Electric AG
01.04.09/rut
Frauenfeld, Switzerland
DABU AD2T-2Q:
Sensor side
PIN Signal
Description
1
Exc. +
S/G1
2
Sig. -
S/G1
3
Sig. +
S/G2
4
Exc. -
S/G2
Control side
PIN Signal
1
+ Vs
2
- Vout
3
GND
4
+ Vout
5
Reset
S/G bridge
4.3
RESET – Function
The RESET - function is used to tare/zero the output signal. Zero shift occur while mounting strain
gage sensors, because of sliding or temperature differences.
It’s possible to tare an output signal up to +/-6mV/V with the amplifier. If the signal is higher than +/-
6mV/V, it is not possible to tare the signal anymore and the LED will turn on.
There are two possibilities to reset the amplifier.
1. Reset by the control via the connector pin 5.
2. Underneath the amplifier cover by pressing the reset button manually.