4 operating instructions – Euphonix 740.0065NA Benutzerhandbuch

Seite 13

Advertising
background image

PHÖNIX Messtechnik GmbH, Salzschlirferstr. 13, D-60386 Frankfurt/M., Germany, Tel: +49/69/416742 -20, Fax: -29

12

Fig. 6a: Connected as a mini switch

For switch type 740.0060 at voltages >24 V remove
the resistor marked with R1 (s. fig. 1).

Please observe limit values (chapter 8) and safety
precautions
(s. fig. 6b).

Fig. 6b: safety precautions for operation in low

DC/AC circuits.

3.2.3 Namur switch

Fig. 7: Connecting of the Namur switch

3.3 Setting the switch position

Before starting-up, the bistable Reed contact must be properly set, in relation to the float in the level
gauge. This can be accomplished by using the control magnet (PHÖNIX part BG10XXXXMAKU, delivered
with liquid level gauges). This is moved up or down along the switch according to figs. 3a and 3b. The
switching function can be tested using an appropriate alarm or ohmmeter on the terminals 1 and 3. In this
case the system voltage, external wires must be disconnected !

4 Operating instructions

4.1 Two-step action with overlap with one PHÖNIX type 740.0060 level switch

Due to the Hysteresis of the bistable level switch type 740.0060 (see chapter 9) it can be used for a two-
step action of liquid levels.

low load

740.0065NA