Scalance x005 technical specifications, Scalance x005 technical specifications -6, 7 scalance x005 technical specifications – Siemens Industrial Ethernet Scalance X005 Benutzerhandbuch

Seite 48

Advertising
background image

Product Characteristics

4.7 SCALANCE X005 Technical Specifications

Port status indicator (green/yellow LEDs)

The status of the ports is indicated by five LEDs:

Status

Meaning

Port 1 to 5 LED lit green

TP link exists, no data reception

Port 1 to 5 LED lit yellow

TP link exists, data received at TP port

Port 1 to 5 LED flashes yellow

Test phase during power on

4.7 SCALANCE X005 Technical Specifications

Technical Specifications of SCALANCE X005

Ports
Attachment of DTEs or network components over

twisted pair

5xRJ-45 sockets with MDI-X pinning 10/100

Mbps (half/ full duplex)

Connector for power supply

1 x 2-pin plug-in terminal block

Electrical Data
Power supply

Power supply DC 18 .. 32 V

safety extra-low voltage (SELV)

Power loss at DC 24 V (typ.)

2 W

Current consumption at rated voltage (typ.)

80 mA

Overvoltage protection at input

PTC resetable fuse (0.5 A / 60 V)

Permitted Cable Lengths
Connection over Industrial Ethernet FC TP

cables
0 –100 m




0 –85 m



Industrial Ethernet FC TP standard cable with IE

FC RJ-45 plug 180

or

over Industrial Ethernet FC outlet RJ-45 with 0 -

90 m Industrial Ethernet FC TP standard cable +

10 m TP cord
Industrial Ethernet FC TP marine/trailing cable

with IE FC RJ-45 plug 180

or

0 - 75 m Industrial Ethernet FC TP marine/trailing

cable + 10 m TP cord

Aging time

375 seconds

Industrial Ethernet SCALANCE X005

4-6

Commissioning Manual, A2B00051528A

Advertising