3. inTended use

Unauthorized use of the Power I/O Box Type 8643
with FOUNDATION Fieldbus connection can be
dangerous to people, nearby equipment and the
environment.

The device is designed as a valve and sensor connec-

tion. Only sensors and valves may be connected which

comply with the technical specifications.
During use observe the authorized data, the opera-

ting conditions and conditions of use specified in the

contract documents and operating instructions, as

indicated in the EC-Type Examination Certificate (see

Appendix of the Operating Instructions).
The device may be used only in conjunction with third-

party devices and components recommended and

authorized by Bürkert.
Correct transportation, correct storage and installation

and careful use and maintenance are essential for

reliable and faultless operation.
Use the device only as intended.

english

5

explosion protection approval

3.1.

Any unauthorized changes to the Power I/O Box Type 8643
with FOUNDATION Fieldbus connection or to components
invalidate the explosion protection approval.

Predictable misuse

3.2.

Do not subject the housing of the Power I/O Box Type 8643
to mechanical loads (e.g. by placing objects on it or standing
on it).

english

6

4. basic safeTy

insTrucTions

These safety instructions do not make allowance for any:

contingencies and events which may arise during the instal-

lation, operation and maintenance of the devices.
local safety regulations – the operator is responsible for

observing these regulations, also with reference to the
installation personnel.

Hazardous if used in explosion-risk area. Risk of
explosion from electrical voltage!
The Power I/O Box Type 8643 is designed as ignition
protection type Ex-e (increased safety).

Before working on non-intrinsically safe circuits of

the Power I/O Box Type 8643, always switch off the

operating voltage of the system!

Danger of explosion due to internal charging of the
Power I/O Box Type 8643!
When the power supply to the Power I/O Box Type
8643 is switched off, the internally stored charge will not
be completely dissipated for 4 minutes. To prevent an
explosion, switch off the power supply before connecting
or disconnecting Ex-e terminals.

english

7

Do not remove the cover from the connection terminals

for Ex-e switching circuits until the connected Ex-e cir-

cuits have been disconnected from the power supply

for longer than 4 minutes.
If using the 2-wire version in potentially explosive

areas, do not connect any cable to the Power 24 V

supply terminals!

Danger of explosion if the allowable ambient tempe-
rature ranges are exceeded!

Observe the respective ambient temperature range

which is based on the type designation (e.g. 8643-2-

AL-KS-F-I/O), according to the table in the EC-Type

Examination Certificate (see Appendix of the Opera-

ting Instructions / Type Examination Certificate).

Danger of explosion due to unauthorized combi-
nation of the ignition protection types!
Due to unauthorized combination of the ignition pro-
tection types, the device is not suitable for use in the
explosion-risk area. If the device is nevertheless used in
this area, there is a danger of explosion!

If the bus supply of the 4-wire version of the device

was operated once in ignition protection type of

increased safety (e), the bus supply may no longer be

intrinsically safe in the ignition protection type (i).

english