16

Cable gland for earth cable PA
(potential equalisation)

Cable glands for intrinsically safe
circuits (8 screw joints, blue)

Cable glands for bus and power
supply (4 screw joints, black)

Location of the cable connections on the plastic

Fig. 2:

housing of the device

english

17

When delivered, the cable glands are covered
with protective caps. These protective caps must
remain on the cable glands until the cables are
connected to keep out dirt.

diP-switch

6.2.2.

ON

ON

OFF

Switch 1

DIP-Switch

Fig. 3:

Switch 1 - ON:
Simulate can be locked so that the READBACK_D is over-
written in the DO_valve function block.

english

18

led-display

6.2.3.

LED 1 green

LED 2
green

LED 3 red

LED-Module
(optional)

LED 1

is lit when voltage is applied to the bus
supply.

LED 2

is lit if the device is using cyclic data transfer.

LED 3

is lit if the device is not using cyclic data
transfer (only after Power on or if the
Watchdog is active).

Location of the LED-Display

Bild 1:

If neither LED 2 nor LED 3 is lit, check power
supply!

english

19

Technical daTa

7.

General Technical data

7.1.

Values for 2 and 4-lead versions
Housing material

Polyester, aluminium

Cable entry

Polyamide cable fittings

Degree of protection

IP65 (DIN EN 60529)

Protection class

3 (DIN EN 61140(VDE 0140-1))

Ignition protection identi-
fication (entire device)

II 2 (1) G Ex [ia] me IIC T

Inputs

8, intrinsically safe, NAMUR
(according to EN 60947-5-6)

Outputs

4, intrinsically safe

Outputs for pilot valves:

Min. switching current

30 mA (Power reduction on
holding current after min. 50 ms)

Min. holding current

15 mA

Internal resistance

330 Ohm

Open-circuit voltage

24 V

english

Type 8643