Burkert Type 8643 Benutzerhandbuch

Seite 8

Advertising
background image

28

cable glands

8.3.

Warning!

Danger of explosion!
No explosion protection if cable glands are defective or
wrong.

Replace defective cable glands only with Ex-autho-

rized (Ex e II) cable glands with adequate application

temperature range (see Appendix of the Operating

Instructions / Type Examination Certificate).

At the factory all cable glands are sealed with a

plug (protection class IP65).
Seal all unused cable glands with a plug to

maintain IP protection (IP65).

english

29

M16x1.5 potential equalisation
PA (with plastic housing)

4 black M20x1.5 cable glands bus and power
supply

8 blue M20x1.5 cable glands for intrinsically
safe circuits (sensor/actuator outputs)

Cable glands on the metal housing

Fig. 4:

The housing features eight blue cable glands for the intrin-
sically safe circuits and four black glands for the bus and
power supply with increased safety.
The bus and power supplies each have two M20x1.5
glands to loop through the supply lines.

english

30

For sensors and actuators each output (with two sensors)
has an M20x1.5 cable gland.

Devices with plastic housing have an M16x1.5 cable
gland for the internal earth connection (PA).
Devices with metal housing (e.g. aluminium) have an
earth connection on the outside of the housing.

electrical connections

8.4.

safety instructions

8.4.1.

note!

Incorrect polarity!
No function if reverse polarity.

Pay attention to the polarity of the terminals!

The device is protected against polarity reversal.

english

31

overview of the terminals and

8.4.2.

outputs

LED module

Address

BUS

Power supply 24 V DC
(4-wire device only)

Bus

Shield

Actuators and Sensors

Overview of terminals and outputs

Fig. 5:

english

Type 8643