6. Commissioning, operation

14083458.01 09/2013 GB/D

WIKA operating instructions models TR12, TC12 (Ex i)

18

WARNING!

Thermometers must be earthed if dangerous voltages could be expected at the

connection wires (caused, for example, by mechanical damage, electrostatic

discharge or induction)!

6.1 Electrical connection

CAUTION!

Damage to cables and wires, and to connection points must be avoided

Leads with bare ends must be finished with end splices (cable preparation)

Both the internal effective capacitance and inductance must be considered

The electrical connection is to be made according to the sensor connections shown below:

Resistance thermometer

1 x Pt100, 2-wire

1 x Pt100, 3-wire

1 x Pt100, 4-wire

2 x Pt100, 2-wire

red

white

white

red

2 x Pt100, 3-wire

red

white

white

red

red

yellow

white

yellow

black

white

red

black

black

red

red

3160696.01

3171966.01

Single

thermocouple

Dual

thermocouple

Colour code of cable

Sensor

type

Standard

Positive Negative

K

DIN EN 60584

green

white

J

DIN EN 60584

black

white

E

DIN EN 60584

violet

white

N

DIN EN 60584

pink

white

Thermocouples