WIKA operating instructions models TR12, TC12 (Ex i)

12

Measuring point insulated (ungrounded)

Measuring point not insulated (grounded)

Thermocouple

Thermocouple

Measuring point

Measuring point

Sheath

Sheath

Tolerance value

For the tolerance value of thermocouples, a cold junction temperature of 0 °C has been

taken as the basis. When using a compensating cable or thermocouple cable, an additional

measuring deviation must be considered.

For tolerance values and further specifications, see the corresponding WIKA data sheet

and Technical Information IN 00.23, “Application of thermocouples”.

For further important safety instructions for operation in hazardous areas, see

chapter 7 “Information on mounting and operation in hazardous areas”.

4. Design and function

4.1 Description

The model TR12-B (resistance thermometer) and model TC12-B (thermocouple) electrical

thermometers consist of a module (TR12-M, TC12-M) which is built into a housing. The

module is made up of a spring-loaded measuring insert (TR12-A, TC12-A) built into a neck

tube. The measuring insert (TR12-A, TC12-A) is replaceable.

Sensor design in TR12-A, TR12-B, TR12-M:

The measuring resistor is embedded in ceramic powder, heat-resistant potting compound,

cement compound or thermally conductive paste. A one-sided sealed tube, which is welded

to a mineral-insulated cable, forms the external shell of the sensor tip of the measuring

insert.

Sensor design in TC12-A, TC12-B, TC12-M:

The measuring insert of the thermocouple is manufactured from mineral-insulated cable.

The thermocouple consists of the internal leads of the mineral-insulated cable. The weld

spot of the thermocouple is, depending on the design, either ungrounded welded with the

sheath of the mineral-insulated cable or grounded welded.

If the temperature sensor is designed as a grounded thermocouple, the thermocouple is

joined directly to the sheath. Designs with a diameter smaller than 3 mm and with grounded

thermocouples should be considered as galvanically connected with earth potential.