WIKA operating instructions models TR12, TC12 (Ex i)

30

8.3 Variant 3:

ATEX/IECEx Ex i certified temperature transmitters.

The evaluation is carried out over a current (4 … 20 mA), voltage (0 … 10 V) or field bus

signal, which is generated from an ATEX/IECEx Ex i certified temperature transmitter.

Use in zone 1, marking II 2G Ex ia IIC Gb

The housing or the connection head is in zone 1 (or zone 2). The sensor is located in

zone 1.

The main marking for models TR12-B and TC12-B are found on the certified connection

housing or Ex i field transmitter.

The TR12-M and TC12-M modules are marked through a foil plate on the neck tube.

For a possible use at the partition to zone 0 with a thermowell, the approvals and conditions

of the relevant Ex i field transmitters must be followed.

Temperature class classification, ambient temperatures

For the measuring insert with neck tube, the following ambient temperature range applies:

(-50)

1)

-40 … +85 °C

1) The value in brackets applies only for specific low-temperature designs.

The permissible ambient temperatures of the certified Ex i field transmitter must be taken

from the respective operating instructions or data sheets. Through deviations in temperature

ranges, limitations can occur.

8.4 Use in methane atmospheres

As a result of the higher Minimum Experimental Safe Gap (MESG) and Minimum Ignition

Current (MIC) of Methane, the instrument can also be used in hazardous gas atmospheres

caused by this.

U

i

= see third-party transmitter approval

I

i

= see third-party transmitter approval

P

i

= see third-party transmitter approval

L

i

= see third-party transmitter approval

C

i

= see third-party transmitter approval

9. Calculation examples for self-heating at the thermowell tip

The self-heating at the thermowell tip depends upon the sensor type (TC/RTD), the

measuring insert diameter and the thermowell design. The table below shows the possible

combinations. The heating at the sensor tip of the bare measuring insert is clearly higher;

the representation of these values was omitted on the grounds of the required assembly

with a thermowell.