WIKA operating instructions models TR31-3, TR31-K

Explanation of symbols

Before mounting and commissioning the instrument,

ensure you read the operating instructions!

CE, Communauté Européenne

Instruments bearing this mark comply with the relevant

European directives.

3. Specifications

Thermometer with transmitter and output signal 4 ... 20 mA

(model TR31-x-x-TT)

Temperature range

without neck tube -50 ... +150 °C

(-58 ... +302 °F), with neck tube

-50 ... +250 °C (-58 ... +482 °F)

1) 2)

Measuring element

Pt1000

Connection method

2-wire

Tolerance value of the measuring

element

Class A

3)

(per IEC 60751)

Measuring deviation of the

transmitter

±0.25 K

(per IEC 60770)

Total measuring deviation in

accordance with IEC 60770

Measuring deviation of the measuring

element + the transmitter

Measuring span

minimum 20 K, maximum 300 K

Basic configuration

Measuring range 0 ... 150 °C

(-32 ... +302 °F), other measuring

ranges are adjustable

Analogue output

4 ... 20 mA, 2-wire

Linearisation

Linear to temperature per IEC 60751

Linearisation error

±0.1 %

4)

Switch-on delay, electrical (time

before the first measured value)

max. 4 s

Warming-up period

After approx. 4 minutes, the instrument

will function to the specifications

(accuracy) given in the data sheet.