Commissioning, operation – WIKA TR31 Benutzerhandbuch

Seite 21

Advertising
background image

GB

WIKA operating instructions models TR31-3, TR31-K

14096788.01 07/2014 GB/D

21

6. Commissioning, operation

6.3 Behaviour of the electrical output signal 4 ... 20 mA

Sensor break and short-circuit

Sensor break or short-circuit are signalled after positive detection

(after approx. 1 second). If this fault condition has been caused by

a malfunction, then a relevant measurement signal must exist for

approx. 1 second in order to return to measuring mode. From the time

of the error detection up to the fault signal, the last relevant measured

value will be delivered on the current loop.

Therefore, in the event of a “true” sensor break or short-circuit, this

is also signalled permanently. In the event of a “false” sensor break

or short-circuit, the transmitter has the possibility of reverting to

measuring mode.

Medium temperature outside the span

If the media temperature configured in the transmitter exceeds

the span, the transmitter will operate in a linear fashion within the

following limits: 3.8 mA (MRS); 20.5 mA (MRE). If these limits are

exceeded, then an error will be signalled.

0

10

24 30 36

1083

833
583

Load diagram

The permissible load depends on the loop supply voltage. For

communication with the instrument with programming unit PU-448, a

max. load of 350 Ω is admissible.

Voltage U

B

in V

Load R

A

in

Ω