WIKA operating instructions models TR31-3, TR31-K

7. Configuration

The measuring range is configurable between -50 ... +250 °C

(-58 ... +482 °F). The configuration software checks the required

measuring range and will only accept permissible values. Intermediate

values are configurable; the smallest increment is 0.1 °C or 0.1 °F.

The

thermometers are delivered configured to customer specifications within

the configurable limits.

Please note:

The measuring range of the thermometer is limited by the application

range of the measuring element, not by the setting range of the

transmitter.

Maximum permissible temperatures:

Without neck tube: -50 … +150 °C (-58 ... +302 °F)

With neck tube: -50 … +250 °C (-58 ... +482 °F)

1)

At case with transmitter: 85 °C (185 °F)

With directly connected cable: -20 ... +80 °C (-4 ... +176 °F)

1) Version with mineral-insulated sheathed cable can be used up to 300 °C (572 °F).