9. Parameterization plan

Zl 11-17

Status for lines 1-7

0

Parameter change enabled

1

Parameter lock (entry,clearing)

2

Skip parameter

Line 22

Operating modes

0

Step preset

1

Main preset

2

Parallel comparison

3

P1-dragged preset

Line 24

Decimal point

0

No decimal point

1

00000.0

2

0000.00

3

000.000

4

00.0000

Line 25

Count mode

0

Track A resp. UP/DOWN-signal on track B

1

Subtracting (A-B)

2

Adding (A+B)

3

Track A 90° B single evaluation

4

Track A 90° B double evaluation

5

Track A 90° B four times evaluation

Line 26

Frequency main counter track A

0

10 kHz

1

25 Hz

2

3 Hz

Line 27

Frequency main counter track B

0

10 kHz

1

25 Hz

2

3 Hz

Line 28

Input logic

0

PNP - Trigger threshold 10V

1

NPN - Trigger threshold 10V

2

PNP - Trigger threshold 5V

3

NPN - Trigger threshold 5V

4

PNP - Trigger threshold 2,5V

5

NPN - Trigger threshold 2,5V

Line 29

Reset main counter (control input 1)

0

Automated reset and ext. static

1

Automated reset and ext. differntiated

2

Extern static

3

Extern differentiated

4

Extern with "Start-functionality"

Line 31

Functionality control input 2

0

Stop

1

Hold

2

Keylock

3

Hour counter on/off

4

Offset

5

Print (only with interface)

Line 33

Digital output logic

0

Both outputs normally closed

1

P1 Normally open, P2 Normally closed

2

P1 Normally closed, P2 Normally open

3

Both outputs Normally open

Line 35

Latch signal duration P1

0.25

Default

0.01

Min.

99.99

Max.

Line 36

Latch signal duration P2

0.25

Default

0.01

Min.

99.99

Max.

Line 37

Preset P1, P2 adoption

0

Immediately effective

1

After reset

Line 38

Counting range P1,P2 and SC

0

Only positive

1

Positive and negative

Line 39

Function key assignment

0

Not operational

1

XP

2

P1

3

P2

4

SC

5

Σ

6

§

7

SF

Line 40

Code

0000

Code not active

:

9999

Line 41

Functionality batch counter

0

Totalizer

1

When achieving P2

Line 42

Multiplier batch counter (Line 41=1)

1

Default

0

Min.

999

Max.

Line 43

Offset

0

No offset

:

999999

Max. offset

Line 44

Power loss warning

0

No warning

1

warning (display flashing)

Line 51

Baudrate

0

4800 Baud

1

2400 Baud

2

1200 Baud

3

600 Baud

Line 52

Parity

0

Even Parity

1

Odd Parity

2

No Parity

Line 53

Stoppbits

0

1 Stoppbit

1

2 Stoppbits

Line 54

Adresse

00

Default

00

Min.

99

Max.

Line 55

Output assignment via interface
Line 31=5

0

Displayed value

1

XP

2

P1

3

P2

4

SC

5

Σ

6

§

7

SF

Line 56

RS422: connections TxD+ , TxD-

0

In transmission direction during trans-
mission, in receiving direction upon
receipt

1

Ever in transmission direction