Figure 3: Opening the safety switch
Functional check
Warning! Danger of fatal injury as a result of
faults in installation and functional check.
Before carrying out the functional check, make
sure that there are no persons in the danger
area. Observe the valid accident prevention
regulations.
After installation and any fault, the safety function
must be fully checked. Proceed as follows:
Mechanical function test
The actuator must slide easily into the actuating
head. Close the safety guard several times to check
the function.
Electrical function test
1. Switch on operating voltage.
2. Close all safety guards.
The machine must not start automatically.
3. Enable operation in the control system.
4. Open the safety guard.
The machine must switch off and it must not be
possible to start it as long as the safety guard is
open.
Repeat steps 2 - 4 for each safety guard.
Subject to technical modifications; no r
esponsibility is accepted for the accuracy of this information. © EUCHNER GmbH + Co. KG
091210-03-10/11 (translation of the original operating instructions)
Inspection and service
If damage or wear is found, the complete
switch and actuator assembly must be
replaced.
Replacement of individual parts or assemblies
is not permitted!
Note: The year of manufacture can be seen in the
bottom, right corner of the rating plate.
No servicing is required, but regular inspection
of the following is necessary to ensure trouble-free
long-term operation:
correct switching function
secure mounting of components
dirt and wear
loose plug connectors.
Exclusion of liability under the following
circumstances
incorrect use
non-compliance with safety regulations
installation and electrical connection not
performed by authorized personnel
failure to perform functional checks.
EC declaration of conformity
The manufacturer named below herewith declares
that the product fulfills the provisions of the
directive(s) listed below and that the related
standards have been applied.
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen, Germany
Directives applied:
Machinery directive 2006/42/EC
Standards applied:
EN 60947-5-1:2004 + Cor.:2005 + A1:2009
EN 1088:1995+A2:2008
Leinfelden, July 2010
Dipl.-Ing. Michael Euchner
Director
Duc Binh Nguyen
Authorized representative empowered to draw up
documentation
The signed EC declaration of conformity is included
with the product.
Technical data
Parameters
Value
Housing material
Reinforced thermoplastic
Deg. of prot. acc. to IEC 60529 IP 67, mating connector plugged
Mechanical life
2x10
6
operations
Ambient temperature
-20 ... +55°C
Installation position
Any
Approach speed, max.
20 m/min
Actuating force
inserting
8 N
removing
25 N
Weight
0.16 kg
Switching principle
2 positively driven NC contacts, slow-
action switching contact
EMC protection requirements
Acc. to EN 50295 (AS-Interface
standard) and IEC 62026
Connection
M12 plug connector
AS-Interface data acc. to
EA code: 7
AS-Interface specification 2.1
ID code: B
Total current consumption, max. 45 mA
Valid AS-Interface addresses
1 - 31
AS-Interface inputs
In accordance with AS-Interface Safety
at Work
Positively driven NC contact 1
D0, D1
Positively driven NC contact 2
D2, D3
AS-Interface outputs
D1
Red LED, 1 = LED on
D2
Green LED, 1 = LED on
AS-Interface LED Power
Green, AS-Interface voltage present
AS-Interface LED Fault
Red, offline phase or address 0
Reliability values according to EN ISO 13849-1
B
10d
3 x 10
6
40
30
31
3
∅ 4,1
∅ 5,1
V
M=0,6Nm
16
35
43
125
42
3,
5
32
31
16
M=0,6Nm
h
0,3 A
0,3 B
A
B
A
A
13
A-A
LED Power
LED Fault
Insertion depth
Fixed positioning
for safety-related
applications
(screw M5)
Inser
tion depth
Plug connector
not aligned
Order actuator separately
Figure 4: Dimension drawing
Necessary minimum travel + permissible overtravel
Approach direction
Actuator
Actuator
Standard
Overtravel
Horizontal (h)
28 + 2
28 + 7
Vertical (v)
29.5 + 1.5
29.5 + 7
Figure 5: Min. door radii
Hinged actuator P-LR / P-LRN
R > 100
Hinged actuator P-OU / P-OUN
12
26
20
35
28
+2
R > 90
Actuator type
Door radius min. [mm]
Actuator P-G...
1,000
Actuator P-W...
1,000
HINGED ACTUATOR P-OU...
90
HINGED ACTUATOR P-LR...
100