Service and inspection, Technical data – EUCHNER CES-A-V1B-01B-AS1 Benutzerhandbuch

Seite 5

Advertising
background image

Operating Instructions Evaluation Unit CES-A-V1B-01B-AS1

Service and inspection

No servicing is required on the battery-less actuator,

but regular inspection of the following is necessary

to ensure trouble-free long-term operation:

f

Secure fastening of the actuator and the read head

(use of safety screws included)

f

Sealing of the plug connector on the evaluation unit

f

Loose cable connections on the evaluation unit

f

Switch-off distance check

f

A function test should be performed at least once

a year.

f

Shorter intervals may be necessary depending on

the specific application.

Exclusion of liability under the following

conditions:

f

if the unit is not used for its intended purpose

f

non-compliance with safety regulations

f

mounting and electrical connection not performed

by authorized personnel

f

non-implementation of functional checks.

f

if modifications are made.

Su

bj

ec

t t

o

te

ch

ni

ca

l m

od

ifi

ca

tio

ns

; n

o

re

sp

on

si

bi

lit

y

is

a

cc

ep

te

d

fo

r t

he

a

cc

ur

ac

y

of

th

is

in

fo

rm

at

io

n.

©

E

UC

HN

ER

G

m

bH

+

C

o.

K

G

0

96

87

0-

05

-0

9/

12

(t

ra

ns

la

tio

n

of

th

e

or

ig

in

al

o

pe

ra

tin

g

in

st

ru

ct

io

ns

)

Sa

fe

ty

gu

ar

d

Bi

t s

eq

ue

nc

e

on

AS

-In

te

rf

ac

e

bu

s

LE

D

S

TA

TE

(g

re

en

)

LE

D

O

UT

/E

R

R

O

R

(y

el

lo

w

)

LE

D

O

UT

/E

R

R

O

R

(r

ed

)

State

Normal operation

closed

safe code

sequence

on

on

off

Door closed

open

0000

on

off

off

Door open

X

1)

0000

off

off

on

Error, device-internal failure or excessively high

interference

X

1)

0000

once

flashing 3 times

off

off

System check (on switch on)

1) X = safety guard open or closed

Table 1: System states

Programming

State

D0, D1

D2, D3

Monitor diagnosis

2-channel

dependent

Synchronization

time

0.5 s

Safety guard closed

Code sequence

Safe

Green in ASIMON

Safety guard open,

transponder

only half-read

Half-sequence

00

Not safe

Yellow flashing

in ASIMON

Safety guard open,

transponder

only half-read

00

Half-sequence

Not safe

Yellow flashing

in ASIMON

Safety guard open

00

00

Not safe

Red in ASIMON

Address 0 or

communication disrupted

Gray

Table 2: Troubleshooting
With the read heads CES, CEM and CET, two processors each read the transponder in the actuator. Fasten-

ing the actuator in the operating distance with small hysteresis can lead to even slight vibrations causing

the transponder to be read by only one processor (half-reading). This causes the ”yellow flashing“ state to

be indicated.
It is recommended to fasten the actuator in the operating distance so that the hysteresis is adequately large

(Figure 3). If this cannot be realized, the ”dual-channel dependent with filtering“ module can be used in the

ASIMON software. More detailed information about this can be found in the ASIMON software manual, which

can be opened via the Help function of the ASIMON software.

Technical data

Parameter

Wert

Housing material

Plastic

Degree of protection according

to IEC EN 60529:2000

IP67

Ambient temperature

0...+50°C

Weight

Approx. 0.4 kg

Operating voltage

DC 24 V +10% -15%

ower supply unit with safe isola-

tion (IEC 61558-2-6:1998)

Current consumption, max.

(via auxiliary power)

600 mA

AS-Interface data acc. to

AS-Interface specification 2.1

EA code: 7

ID code: B

Operating voltage AS-Interface DC 22.5 ...31.6 V
Total current consumption, max 100 mA
Valid AS-Interface addresses

1 - 31

AS-Interface inputs

Acc. to AS-Interface Safety at Work

CES input IN

(CES read head, M12 socket

5-pin)

AS-Interface bit D0 - D3

Dwell time min.

0.5 s

AS-Interface Outputs
Current consumption max.

600 mA

Output OUT

(for CEM/CET magnet

M12 socket 5-pin)

AS-Interface bit D0

Times
Time-delay max.

From state change

180 ms

Risk time

2)

180 ms

Difference time (for the two

dependent AS-Interface

120 ms

Ready delay

3 s

Distances

3)

min.

typ.

max.

Safe switch-off distance s

ar

-

-

32 mm

Cable length l = 0 ... 25 m

Switch-on distance s

a0

Switching hysteresis

10 mm

0.5 mm

17 mm

2 mm

-

-

Cable length l ≥ 25 ... 50 m

Switch-on distance s

a0

Switching hysteresis

8 mm

0.4 mm

14 mm

1.6 mm

-

-

Reliability values according to EN ISO 13849-1
Category

4

Peformance Level (PL)

e

PFH

d

6,5 x 10

-9

2) According to EN 60947-5-3:2000
3) With evaluation unit CES-A-V1B-01B-AS1 in conjunction with read

head CES-A-LNA...AS1 or CES-A-LNA-SC and actuator CES-A-BBA

on surface mounting of the read head and the actuator.

If installed flush, the switching distance changes as a function of

the installation depth and the safety guard material.