Safety information and Maintenance

(Part of the Operating Instructions for Safety System CES-AH-C03-AH)

Correct use

The Coded Electronic Safety switches series CES

are safety devices for monitoring movable safety

guards so that:

f

dangerous work on machines can only be carried

out if the safety guard is closed.

f

a stop instruction is triggered if the safety guard is

opened when the machine is running.

Before safety switches are used, a risk assessment

must be performed on the machine, e.g., in accor-

dance with:

f

EN ISO 13849-1, Safety of machinery. Safety re-

lated parts of control systems. General principles

for design, Annex B

f

EN ISO 14121, Safety of machinery. Risk assess-

ment. Principles

f

IEC 62061, Safety of machinery. Functional safety

of safety-related electrical, electronic and program-

mable electronic control systems.

Correct use includes compliance with the relevant re-

quirements for installation and operation, for example

f

EN 1088, Safety of machinery. Interlocking devices

associated with guards. Principles for design and

selection

f

EN 60204-1, Safety of machinery. Electrical equip-

ment of machines. General requirements

The safety switch must be used only in conjunction

with the designated CES actuators from EUCHNER.

On the use of different actuators, EUCHNER provides

no warranty for safe function.
A combination of other CES devices or devices from

other manufacturers is not allowed.

Exclusion of liability and warranty

In case of failure to comply with the conditions for

correct use stated above, or if the safety instructions

are not followed, or if any servicing is not performed

as required, liability will be excluded and the war-

ranty void.

General safety instructions

The device is only allowed to be installed and placed

in operation by authorized personnel

f

who are familiar with the correct handling of safety

components,

f

who are familiar with the applicable regulations on

health and safety and accident prevention

f

and who have read and understood the operating

instructions and the system manual.

The safety function of the system while the machine

is in operation can no longer be ensured if the device

is connected incorrectly or used incorrectly.
Prior to use, read the operating instructions on the

CD/DVD supplied, and keep these in a safe place.
Ensure the operating instructions are always avail-

able during mounting, setup and servicing.
EUCHNER cannot provide any warranty in relation to

the readability of the CD/DVD for the storage period

required. For this reason you should archive a printed

copy of the operating instructions. You can download

the operating instructions at www.EUCHNER.de.

Operating instructions on CD/DVD

Each device is supplied with operating instructions

on CD/DVD; these instructions contain detailed infor-

mation on the overall system. The following system

requirements must be met to be able to open or print

the document:

f

PC with PDF Reader installed

f

CD/DVD drive

f

Opening and printing the documents

Important: the autoplay function for the drive must be

enabled (see operating system help) and you will need

a PDF Reader that can open PDF files from version 4.
1. Insert CD/DVD

¨

Selection table is opened in the browser

2. Click the related document for your system

¨

The document is opened and can be printed

Mounting, setup and troubleshooting

For detailed instructions on mounting, setup and

troubleshooting, please refer to the operating instruc-

tions on the CD/DVD.

Electrical connection

For detailed information on the electrical connec-

tion, please refer to the operating instructions on

the CD/DVD.

Important: Two switching elements are connected

in series in the device. Both outputs can therefore

be used separately as a safety output for the direct

interruption of the supply of power to an actuator

(valve, contactor, etc.).
Do not use a control system with pulsing to test the

output cables or switch off the pulsing function in

your control system.
Take note of the connection example in the operating

instructions on CD/DVD.

Inspection and service

Danger! Loss of the safety function because of

damage to the system. In case of damage, the

related component must be replaced completely.

Replacement of individual parts of a component

(e.g. parts of the evaluation unit) is not permitted.

Subject to technical modifications; no r

esponsibility is accepted for the accuracy of this information. © EUCHNER GmbH + Co. KG

106596-05-12/13 (translation of the original operating instructions)

Regular inspection of the following is necessary to

ensure trouble-free long-term operation:

f

Check the switching function

f

Check the secure fastening of the devices and the

connections

f

Check for soiling (e.g. the ventilation slots on the

housing)

Check the safe function of the safety guard par-

ticularly

f

after any setup work

f

after the replacement of a CES component

f

after an extended period without use

No servicing is required, repairs to the device are only

allowed to be made by the manufacturer.

Technical data (extract)

Parameter

Value

min.

typ.

max.

Operating voltage U

B

(reverse polarity

protected, regulated, residual ripple
< 5 %)

20 V

-

28 V

Current consumption

150 mA

External fuse (operating voltage)

0.25 A

-

10 A

Safety outputs LA/LB

Semiconductor outputs,

p-switching, short circuit-

proof

- Output voltage U(LA)/U(LB)

1)

HIGH

U(LA)/ U(LB)

U

B

-1.5 V

-

U

B

LOW

U(LA)/U(LB)

0 V

4 V

Switching current per safety output

0.03 A

-

4 A

Reliability figures according to EN ISO 13849-1
Category

3

Performance Level (PL)

d

PFH

d

1.03 x 10

-7

/ h

Mission time

20 years

1) Values at a switching current of 4 A without taking into account
the cable lengths.

Assured switch-off distance S

ar

Actuator

S

ar

[mm]

CES-A-BBA-...

40

CES-A-BPA-...

58

CES-A-BRN-...

75

Connection example

Internal

logic

UB

7

+LB

5

+LA

4

START

2

LA

3

LB

6

NC

1

NC

9

0V

8

START

Feedback

loop

Feedback

loop

U

B

GND

1)

2)

1)

2)

Advertising