Setup interface and fine calibration

Setup interface

The setup interface is available for configuring the transmitter from
a PC. Connection is via the PC interface with TTL/RS232 converter
and adapter. The protective cover must be pushed on again after
programming.

Configurable parameters:

- TAG number (10 characters)

- sensor type

- connection circuit (2-/3-/4-wire circuit)

- external or internal cold junction

- customized linearization

- range limits

- output signal rising/falling (reversed)

- digital filter

- response on probe break/short-circuit

- recalibration (fine calibration)

- lead resistance for 2-wire circuit

If no supply unit (supply isolator) is available, the 2-wire transmitter
can also be configured using a 9V block battery as a power source.

Fine calibration

Fine calibration means the adjustment of the output signal. The sig-
nal can be adjusted within ± 5% of 20mA full scale. Fine calibration
can be performed through the setup program. Values for 4 mA
(zero) and 20 mA (full scale) and offset can be calibrated separately
using the setup program.