22

Calibrationprocedure

Whenthe

displayshows

Action/Description

ENT

ï

Put the instrument in setup mode

1.10

While the software version number is flashing,
remove the security link and press

ENT

AnLg

Display indicates that unit is /AR type, press

ENT

CIPn

Press Å or ì to Calibrate the inputs or ENT to skip

CIPy

Calibrate inputs?

Start

No

Connect the RTD Simulator to the inputs (for connections see over page).

OPEN

Leave inputs 2 & 3 open circuit

Calibrate

Skip

20.00

Connect 50 Ω resistor

Calibrate

Skip

5.00

Connect 200 Ω resistor

Calibrate

Skip

1.00

Connect 1 kΩ resistor

Calibrate

Skip

0.20

Connect 5 kΩ resistor

Calibrate

Skip

rCLy

Calibrate RTD Sensor?

Start

No

0C

Set the RTD Simulator to 0 °C

Calibrate

Skip

200C

Set the RTD Simulator to 200 °C

Calibrate

Skip

COPn

Press Å or ì to Calibrate the outputs or ENT to skip to the next setup item

Whenthe

displayshows

Action/Description

м

Е

ENT

Put the instrument in setup mode and scroll through the main menu

COPn

Press

Å

or

ì

COPy

Calibrate Outputs?

Toggle

Start

Measure the output current

I=0

The output current should be 0.00 mA
(Use the keypad to adjust the value as required)

Increase Decrease Accept

I=20

The output current should be 20.00 mA

Increase Decrease Accept

Measure the output voltage

E=0

The output voltage should be 0.00 volts

Increase Decrease Accept

E=10

The output voltage should be 10.00 volts

Increase Decrease Accept

rng=

Instrument will continue with the setup process

Note: Do not remove the power while the save message is on display.