Calibrationprocedure
Whenthe
displayshows
Action/Description
ENT
ï
Put the instrument in setup mode
1.10
While the software version number is flashing,
remove the security link and press
ENT
AnLg
Display indicates that unit is /AR type, press
ENT
CIPn
Press Å or ì to Calibrate the inputs or ENT to skip
CIPy
Calibrate inputs?
Start
No
Connect the RTD Simulator to the inputs (for connections see over page).
OPEN
Leave inputs 2 & 3 open circuit
Calibrate
Skip
20.00
Connect 50 Ω resistor
Calibrate
Skip
5.00
Connect 200 Ω resistor
Calibrate
Skip
1.00
Connect 1 kΩ resistor
Calibrate
Skip
0.20
Connect 5 kΩ resistor
Calibrate
Skip
rCLy
Calibrate RTD Sensor?
Start
No
0C
Set the RTD Simulator to 0 °C
Calibrate
Skip
200C
Set the RTD Simulator to 200 °C
Calibrate
Skip
COPn
Press Å or ì to Calibrate the outputs or ENT to skip to the next setup item
Whenthe
displayshows
Action/Description
м
Е
ENT
Put the instrument in setup mode and scroll through the main menu
COPn
Press
Å
or
ì
COPy
Calibrate Outputs?
Toggle
Start
Measure the output current
I=0
The output current should be 0.00 mA
(Use the keypad to adjust the value as required)
Increase Decrease Accept
I=20
The output current should be 20.00 mA
Increase Decrease Accept
Measure the output voltage
E=0
The output voltage should be 0.00 volts
Increase Decrease Accept
E=10
The output voltage should be 10.00 volts
Increase Decrease Accept
rng=
Instrument will continue with the setup process
Note: Do not remove the power while the save message is on display.