Setupsequence – Weidmuller CNDAR - Universal galvanically isolated signal converter Benutzerhandbuch

Seite 23

Advertising
background image

2

•SetupSequence

Setting

Display

Description

Е м

ENT

S/W Version

1.10

S/W Version 1.10

(Note: this information only applies to versions 1.10

to 1.19)

DisplayandInputs

Probe

Conductance

range

rng=

0.20

1.00

5.00

20.00

Introduces the setting
200 µS range
1 mS range
5 mS range
20 mS range

Toggle

Accept

Input range

(for analogue

output)

IPL=

0.00

Input level for analogue output low
e.g., 0.00 mS

-

Dec

-

Inc

Next

Accept

IPH=

10.00

Input level for analogue output high
e.g., 10.00 mS

-

Dec

-

Inc

Next

Accept

Damping factor

dF=

2

Introduces the damping factor
Value, e.g., 2

-

Dec

-

Inc

Next

Accept

Probe factor

pF=

1.00

Introduces the probe factor
Value, e.g., 1.00

-

Dec

-

Inc

Next

Accept

Temperaturecompensation

Compensate for

temperature?

Cenb

Cdsd

Enable
Disable

Toggle

Accept

Number of

breakpoints

nP=

4

Introduces number of linearisation points
Value, e.g., 4

-

Dec

-

Inc

Next

Accept

Breakpoints

H1=

0.0

r1=

0.80

...

H4=

100.0

r4=

20.0

Introduces breakpoint 1 temperature (°C),
e.g., 0.0 °C
Introduces breakpoint 1 ratio,
e.g., 0.80
...
Introduces last breakpoint temperature (°C)
e.g., 100.0 °C
Introduces breakpoint 4 ratio,
e.g., 20.0

-

Dec

-

Dec

-

Dec

-

Dec

-

Inc

-

Inc

-

Inc

-

Inc

Next

Accept

Next

Accept

Next

Accept

Next

Accept

Note: you must at least one ratio of 1.00

(for the reference temperature) or Err will be displayed

Enable/DisableAlarms

Alarms 1 & 2

Select

AL=Y

AL=n

Enable
Disable

Toggle

Accept

Note: alarm settings are only shown if they are enabled.