Connections – Weidmuller PMX400HZX - Display instrument for control panel Benutzerhandbuch

Seite 19

Advertising
background image

1

•Connections

Terminal

Signal

1

Neutral / –

Power supply

2

Live / +

3

Output +

Analogue output
(/AO option only)

4

Output –

5

Common (0V)

Alarm channels one and two are
Solid state switches (max ‘off-state’
voltage = 50 V DC/max ‘on-state’
current = 200 mA )

6

Channel one output

7

Channel two output

8

Link to 12 to allow access to set-up mode (normally left unconnected)

9

Pull (Link to 12 for pull-up/Link to 10 for pull-down)

Inputs

10

Signal –

11

Signal +

12

Regulated 12 V DC out (Ov is connected to pin 10 internally)

13

Normally Closed

Alarm channel three
(optional)

14

Common

15

Normally Open

16

Normally Closed

Alarm channel four
(optional)

17

Common

18

Normally Open

Advertising