Outputcalibration, Setupsequence(continued) – Weidmuller PMX400HZX - Display instrument for control panel Benutzerhandbuch
Seite 22

22
Alarmchannelfoursettings*
Coil energisation
A4nE
A4nd
Normally energised
Normally de-energised
Toggle
Accept
Alarm type
A4=L
A4=H
A4=G
A4=S
Low type (active below setpoint)
High type (active above setpoint)
Group alarm
Siren alarm (manual reset mode only)
Toggle
Accept
Note: for group or siren alarms, the setpoint, deadband and timer settings are skipped
Setpoint value
SP1=
50.00
Setpoint value
e.g., 50.00 %
-
Dec
-
Inc
Next
Accept
Deadband value
db1=
10.00
Deadband value
e.g., 10 %
-
Dec
-
Inc
Next
Accept
Timer delay
dL1=
0
Timer delay (set to 0 s to disable)
e.g., no delay
-
Dec
-
Inc
Next
Accept
Calibrationoptions
Calibrate
Output?
COPy
COPn
Skip output calibration
Calibrate outputs
Toggle
Accept
Save values
SAVE
Instrument is saving the changes to the setup and returning to
normal operation
•Outputcalibration
General
The PMX00HZX analogue outputs are calibrated for a specific output
range and type. If you have changed the output range or type you
must follow the procedure given below.
Equipmentrequirements
• An accurate digital multimeter (accurate to 0.0 mV and ±0.1 μA)
TerminalConnectionsforoutputcalibration
CalibrationStage
Signaltype
Terminal
Analogue Current Output
mA output +
3
mA output –
4
Analogue Voltage Output
V output +
3
V output –
4
SetupSequence(continued)