Outputcalibration, Setupsequence(continued) – Weidmuller PMX400HZX - Display instrument for control panel Benutzerhandbuch

Seite 22

Advertising
background image

22

Alarmchannelfoursettings*

Coil energisation

A4nE

A4nd

Normally energised
Normally de-energised

Toggle

Accept

Alarm type

A4=L

A4=H

A4=G

A4=S

Low type (active below setpoint)
High type (active above setpoint)
Group alarm
Siren alarm (manual reset mode only)

Toggle

Accept

Note: for group or siren alarms, the setpoint, deadband and timer settings are skipped

Setpoint value

SP1=

50.00

Setpoint value
e.g., 50.00 %

-

Dec

-

Inc

Next

Accept

Deadband value

db1=

10.00

Deadband value
e.g., 10 %

-

Dec

-

Inc

Next

Accept

Timer delay

dL1=

0

Timer delay (set to 0 s to disable)
e.g., no delay

-

Dec

-

Inc

Next

Accept

Calibrationoptions

Calibrate
Output?

COPy

COPn

Skip output calibration
Calibrate outputs

Toggle

Accept

Save values

SAVE

Instrument is saving the changes to the setup and returning to
normal operation

•Outputcalibration

General
The PMX00HZX analogue outputs are calibrated for a specific output
range and type. If you have changed the output range or type you
must follow the procedure given below.

Equipmentrequirements
• An accurate digital multimeter (accurate to 0.0 mV and ±0.1 μA)

TerminalConnectionsforoutputcalibration

CalibrationStage

Signaltype

Terminal

Analogue Current Output

mA output +

3

mA output –

4

Analogue Voltage Output

V output +

3

V output –

4

SetupSequence(continued)