Setupsequence – Weidmuller PMX400HZX - Display instrument for control panel Benutzerhandbuch

Seite 20

Advertising
background image

20

•SetupSequence

Setting

Display

Description

Е

м

ENT

S/W Version

v1.01

S/W Version 1.01 (Note: this information only applies to
versions 1.00 to 1.09)

Next

Instrument Type

Freq

PMX400/HZX

Next

DisplayandInputs

Display Intensity

HIbr

LObr

High brightness
Low Brightness

Toggle

Accept

Input type

Inp=

LOAC

H AC

LOdC

HIdC

Con

SGL1

SGL2

SGL3

SGL4

Introduces input type
Low level AC signal
High level AC signal
Low level DC signal
High level DC signal
Contact Closure
Special signal - type 1
Special signal - type 2
Special signal - type 3
Special signal - type 4

Next Prev Accept

Input frequency

range

FdP=

.

Decimal point position

Shift

Next

Accept

FLO=

300

Input frequency range lower limit
e.g., 300 Hz

-

Dec

-

Inc

Next

Accept

FHI=

1000

Input frequency range upper limit
e.g., 1 kHz

-

Dec

-

Inc

Next

Accept

Damping factor

dF=

2

Introduces the damping factor
Value, e.g., 2

-

Dec

-

Inc

Next

Accept

Display range

dP=

.

Decimal point position

Shift

Next

Accept

dLO=

0.0

Display range lower limit
e.g., 0.0

-

Dec

-

Inc

Next

Accept

dHI=

100.0

Display range Upper limit
e.g., 100.0

-

Dec

-

Inc

Next

Accept