Setupsequence(continued) – Weidmuller PMX400HZX - Display instrument for control panel Benutzerhandbuch
Seite 21

21
Analogueoutputs*
Analogue output
select
AOPY
AOPN
Enabled
Disabled (Select this option for PMX420)
Toggle
Accept
Output action
OP=d
OP=r
Direct
Reversed
Toggle
Accept
Analogue output
range
OPL=
4.00
Output low value
e.g., 4.00
-
Dec
-
Inc
Next
Accept
OPH=
20.00
Output high value
e.g., 20.00
-
Dec
-
Inc
Next
Accept
Note: to change the output high or low value you must calibrate the outputs.
GeneralAlarmsettings*
Alarms 1 & 2
Select
A12Y
A12n
Enable
Disable
Toggle
Accept
Alarms 3 & 4
Select
A34Y
A34n
Enable
Disable
Toggle
Accept
Setpoint security
SECy
SECn
Setpoints fixed at setup
Can change setpoints
Toggle
Accept
Alarm reset
sequence
nOr
rES
Automatic reset
Manual reset
Toggle
Accept
Note: alarm settings are only shown if the relevant alarm channel is enabled.
Alarmchannelonesettings*
Coil energisation
A1nE
A1nd
Normally energised
Normally de-energised
Toggle
Accept
Alarm type
A1=L
A1=H
Low type (active below setpoint)
High type (active above setpoint)
Toggle
Accept
Setpoint value
SP1=
50.00
Setpoint value
e.g., 50.00 %
-
Dec
-
Inc
Next
Accept
Deadband value
db1=
0.01
Deadband value
e.g., 0.01 %
-
Dec
-
Inc
Next
Accept
Timer delay
dL1=
20
Timer delay (set to 0s to disable)
e.g., 20 s
-
Dec
-
Inc
Next
Accept
Alarmchanneltwosettings*
As alarm channel one, except uses A2nE, A2nd, A2=L,A2=H, SP2=, db2= and dL2=.
Alarmchannelthreesettings*
As alarm channel one, except uses A3nE, A3nd, A3=L,A3=H, SP3=, db3= and dL3=.
SetupSequence(continued)