Terminal
Signal
1
Sense −
Bridge Excitation Voltage
2
Sense +
3
Excitation +
4
Excitation −
6
0 V reference (for calibration only)
Input signal
7
Signal +
8
Signal −
9
Not Used
10
Neutral (−)
Power Supply
11
Live (+)
12
Not Used
13
Output +
Output signal
14
Output −
15,16
Not Used
Case
Earthing is via a stud on lower side of case
Note: The power supply is isolated from the rest of the circuit but input and output circuits share a
common negative return.
− Sense
+ Sense
+ Excitation
− Excitation
+ Signal
− Signal
1 2 3 4
7 8
STG
Input connections for STG with remote sensing excitation.
+ Excitation
− Excitation
+ Signal
− Signal
1 2 3 4
7 8
STG
Input connections for STG with remote sensing disabled.