•Setup

Changingthesetup
For setup mode, connect the security link and press the

Å

and

ì

keys simultaneously. The software version will be displayed (flashing). If
you wish to continue, press within 10 s.
During setup the

Å

and

ì

keys change values and toggle options.

The key accepts changes and moves to the next item in the setup
sequence (see table).
Note: If you remove the security link during the setup sequence, any
changes you have made will be discarded.

SetupSequence

Setting

Display

Description

Е м

ENT

S/W Version

v1.01

S/W Version 1.01 (Note: this information only applies to versions
1.00 to 1.09)

Inputs

Input type

IP=1

IP=E

Current (mA)
Voltage (V)

Toggle

Accept

Maximum

input range

rng=

5

10

20

50

Introduces the setting
-5.500 to +5.500 mA or V
-11.00 to +11.00 mA or V
-22.00 to +22.00 mA or V
-55.00 to +55.00 mA or V

Toggle

Accept

Input range

IPL=

4.00

Input range lower limit
e.g., 4.00 mA

-

Dec

-

Inc

Next

Accept

IPH=

20.00

Input range upper limit
e.g., 20.00 mA

-

Dec

-

Inc

Next

Accept

Input

Calibration?

CIPn

CIPy

Skip input calibration
Calibrate the inputs

Toggle

Accept

Transfer
function

FnC=

LInr

Sr

Introduces the transfer function
Linear
Square root

-

Toggle
Toggle

-

Accept
Accept