Setupsequence(continued) – Weidmuller UPIR - Analog to frequency converter Benutzerhandbuch
Seite 22

22
Low cut-out
settings
CO=y
CO=n
Enable low cut-out
Disable low cut-out
Toggle
Accept
COP=
2.50
Introduces cut-off level in %,
e.g., 2.50 %
-
Dec
-
Inc
Next
Accept
Damping factor
dF=
2
Introduces the damping factor
Value, e.g., 2
-
Dec
-
Inc
Next
Accept
Pulseoutput
Pulse rate
decimal point
PdP=
.
Pulse rate decimal point position
-
Shift
Next
Accept
Pulse rate
timebase
BAS=
SEC
nin
Hrs
Introduces the pulse timebase,
per second
per minute
per hour
-
Toggle
Toggle
Toggle
-
Accept
Accept
Accept
Output duty
cycle
SHP=
30nS
Ensr
Introduces the pulse output duty cycle
Fixed (30 nS) ‘on’ time
even mark/space ratio (50 % duty cycle)
-
Toggle
Toggle
-
Accept
Accept
Pulse output
frequency range
PLO=
0.0
Output range lower limit
e.g., 0.0
-
Dec
-
Inc
Next
Accept
PHI=
100.0
Output range Upper limit
e.g., 100.0
-
Dec
-
Inc
Next
Accept
Alarmchannel
Coil energisation
A1nE
A1nd
Normally energised
Normally de-energised
Toggle
Accept
Alarm type
A1=L
A1=H
Low type (active below setpoint)
High type (active above setpoint)
Toggle
Accept
Setpoint value
SP1=
50.0
Setpoint value
e.g., 50.00 %
-
Dec
-
Inc
Next
Accept
Deadband value
db1=
0.1
Deadband value
e.g., 0.01 %
-
Dec
-
Inc
Next
Accept
Timer delay
dL1=
20
Timer delay (set to 0 s to disable)
e.g., 20 s
-
Dec
-
Inc
Next
Accept
Alarm reset
sequence
nOr
rES
Automatic reset
Manual reset
Toggle
Accept
Setpoint
security
SECy
SECn
Setpoints fixed at setup
Can change setpoints
Toggle
Accept
Save values
SAVE
Instrument is saving the changes to the setup and returning to normal
operation
SetupSequence(continued)