22

Outputcalibrationprocedure

Whenthe

displayshows

Action/Description

м

Е

ENT

Put the instrument in setup mode and scroll through the main menu

COPn

Press

Å

or

ì

COPy

Calibrate Outputs?

Toggle

Start

IP=1

Connect the multimeter to measure the output current

Next

I=0

Press

Å

or

ì

. The output current should be 0.00 mA

(Use the keypad to adjust the value as required)

Increase Decrease Accept

I=20

Press

Å

or

ì

.

The output current should be 20.00 mA

Increase Decrease Accept

Measure the output voltage

E=0

Press

Å

or

ì

. The output voltage should be 0.00 V

Increase Decrease Accept

E=10

Press

Å

or

ì

. The output voltage should be 10.00 V Increase Decrease Accept

Save

Instrument will save values and return to normal operation (using the new values).

Note: Do not remove the power while the save message is on display.

SetupSequence
During setup the

Å

and

ì

keys change values and toggle options.

The ENT key accepts changes and moves to the next item in the setup
sequence).

Setting

Display

Description

Е м

ENT

S/W Version

v4.01

S/W Version 4.01 (Note: this information only applies to versions
4.00 to 4.09)

DisplayandInputs

Input type

IP=

P100

n120

Introduces the input type
Pt100 RTD sensor
Ni120 RTD sensor

Toggle

Accept

Display units

dEgC

dEgF

Degrees Celsius

Degrees Fahrenheit

Toggle