22 outputcalibrationprocedure, Setupsequence during setup the – Weidmuller URTAR - Universal glavanically isolated signal converter Benutzerhandbuch
Seite 22

22
Outputcalibrationprocedure
Whenthe
displayshows
Action/Description
м
Е
ENT
Put the instrument in setup mode and scroll through the main menu
COPn
Press
Å
or
ì
COPy
Calibrate Outputs?
Toggle
Start
IP=1
Connect the multimeter to measure the output current
Next
I=0
Press
Å
or
ì
. The output current should be 0.00 mA
(Use the keypad to adjust the value as required)
Increase Decrease Accept
I=20
Press
Å
or
ì
.
The output current should be 20.00 mA
Increase Decrease Accept
Measure the output voltage
E=0
Press
Å
or
ì
. The output voltage should be 0.00 V
Increase Decrease Accept
E=10
Press
Å
or
ì
. The output voltage should be 10.00 V Increase Decrease Accept
Save
Instrument will save values and return to normal operation (using the new values).
Note: Do not remove the power while the save message is on display.
SetupSequence
During setup the
Å
and
ì
keys change values and toggle options.
The ENT key accepts changes and moves to the next item in the setup
sequence).
Setting
Display
Description
Е м
ENT
S/W Version
v4.01
S/W Version 4.01 (Note: this information only applies to versions
4.00 to 4.09)
DisplayandInputs
Input type
IP=
P100
n120
Introduces the input type
Pt100 RTD sensor
Ni120 RTD sensor
Toggle
Accept
Display units
dEgC
dEgF
Degrees Celsius
Degrees Fahrenheit
Toggle
Accept