Setupsequence(continued) – Weidmuller URTAR - Universal glavanically isolated signal converter Benutzerhandbuch

Seite 23

Advertising
background image

23

Maximum

input range

rng=

Introduces the display range:

-

Next

°C

°F

Range

Sensor

200C

392F

-99.9 to 200.0 °C or

-99.9 to 392.0 °F

Pt100

700C

1292

-200 to 700 °C or

-328 to 1292 °F

320C

608F

-80 to 320 °C or

-112 to 608 °F

Ni120

210C

410F

-80.0 to 210.0 °C or

-99.9 to 410.0 °F

Toggle

Accept

Input range

IPL=

-40

Input range lower limit in display units
e.g., -40 °C

-

Dec

-

Inc

Next

Accept

IPH=

650

Input range upper limit in display units
e.g., 650 °C

-

Dec

-

Inc

Next

Accept

Damping factor

dF=

2

Introduces the damping factor
Value, e.g., 2

-

Dec

-

Inc

Next

Accept

Input

Calibration?

CIPn

CIPy

Skip input calibration
Calibrate the inputs

Toggle

Accept

Important note: do not select input calibration unless you

are fully prepared to complete the entire input calibration sequence.

Enable/DisableAlarms

Alarms 1 & 2

Select

AL=Y

AL=n

Enable
Disable

Toggle

Accept

Note: alarm settings are only shown if they are enabled.

Alarmchannelone

Coil energisation

A1nE

A1nd

Normally energised
Normally de-energised

Toggle

Accept

Alarm type

A1=L

A1=H

Low type (active below setpoint)
High type (active above setpoint)

Toggle

Accept

Setpoint value

SP1=

50.0

Setpoint value
e.g., 50.00 %

-

Dec

-

Inc

Next

Accept

Deadband value

db1=

0.1

Deadband value
e.g., 0.01 %

-

Dec

-

Inc

Next

Accept

Timer delay

dL1=

20

Timer delay (set to 0s to disable)
e.g., 20 s

-

Dec

-

Inc

Next

Accept