Setupsequence(continued) – Weidmuller URTAR - Universal glavanically isolated signal converter Benutzerhandbuch

Seite 24

Advertising
background image

2

Alarmchanneltwo

Coil energisation

A2nE

A2nd

Normally energised
Normally de-energised

Toggle

Accept

Alarm type

A2=L

A2=H

Low type (active below setpoint)
High type (active above setpoint)

Toggle

Accept

Setpoint value

SP2=

50.0

Setpoint value
e.g., 50.0 %

-

Dec

-

Inc

Next

Accept

Deadband value

db2=

10.0

Deadband value
e.g., 10.0 %

-

Dec

-

Inc

Next

Accept

Timer delay

dL2=

20

Timer delay (set to 0 s to disable)
e.g., 20 s

-

Dec

-

Inc

Next

Accept

Generalalarmsettings

Alarm reset

sequence

nOr

rES

Automatic reset
Manual reset

Toggle

Accept

Setpoint

security

SECy

SECn

Setpoints fixed at setup
Can change setpoints

Toggle

Accept

Analogueoutputs

Analogue

Output type

OP=I

OP=E

Current based output
Voltage based output

Toggle

Accept

Analogue output

range

OPL=

4.00

Output low value
e.g., 4.00

-

Dec

-

Inc

Next

Accept

OPH=

20.00

Output high value
e.g., 20.00

-

Dec

-

Inc

Next

Accept

Output action

OP=d

OP=r

Direct
Reversed

Toggle

Accept

Calibrate

Output?

COPn

COPY

Skip output calibration
Calibrate outputs

Toggle

Accept

Save values

SAVE

Instrument is saving the changes to the setup and returning to normal
operation

SetupSequence(continued)