•Calibration

General
The UTC/AR is factory calibrated to a specific output range and format.
During calibration allow a few seconds for signals to stabilise before
accepting the value.
Note: The millivolt source must be connected directly to the input
terminals using copper wire. Remove the CJC board first.
Equipment requirements
• A suitable, stable millivolt source (accurate to 0.0 mV)
• An accurate digital multimeter (accurate to 0.0 mV and ±0.1 μA)

Terminalconnectionsforinputcalibration

CalibrationStage

Signaltype

Terminal

Input circuit

millivolt source +

2

millivolt source −

3

Inputcalibrationprocedure

Whenthe

displayshows

Action/Description

ENT

ï

Put the instrument in setup mode and scroll through the main menu

C Pn

Press

Å

or

ì

C Py

Calibrate inputs?

Start

No

Connect the current source to the inputs (for connections see over page).

E=0

Set the millivolt source to 0.00 mV (and wait a few seconds)

Calibrate

Skip

E=8

Set the millivolt source to 8.00 mV (and wait a few seconds)

Calibrate

Skip

E=15

Set the millivolt source to 15.00 mV (and wait a few seconds)

Calibrate

Skip

E=30

Set the millivolt source to 30.00 mV (and wait a few seconds)

Calibrate

Skip

E=60

Set the millivolt source to 60.00 mV

(and wait a few seconds)

Calibrate

Skip

AL=Y

Continue with the setup sequence.

Note 1: To discard changes to calibration and setup you can remove the power at this point.
Note 2: If the display shows OPEn check that the input simulator is properly connected.