2 terminalconnectionsforoutputcalibration, Outputcalibrationprocedure – Weidmuller UTCAR - Universal glavanically isolated signal converter Benutzerhandbuch

Seite 23

Advertising
background image

2

Terminalconnectionsforoutputcalibration

CalibrationStage

Signaltype

Terminal

Analogue Current Output

mA output +

14

mA output −

15

Analogue Voltage Output

V output +

14

V output −

16

Outputcalibrationprocedure

Whenthe

displayshows

Action/Description

м

Е

ENT

Put the instrument in setup mode and scroll through the main menu

COPn

Press

Å

or

ì

COPy

Calibrate Outputs?

Toggle

Start

OPL=

Connect the multimeter to measure the output (as a current or voltage as
chosen during setup)

Next

1.00

The output current should be at the required zero
value, e.g., 1.00 V for 1-5 V output.
(Use the keypad to adjust the value as required)

Increase Decrease Accept

5.00

The output current should be at the required full
scale value, e.g., 5.00 V for 1-5 V output.
(Use the keypad to adjust the value as required)

Increase Decrease Accept

Save

Instrument will save values and return to normal operation (using the new values).

Note: Do not remove the power while the save message is on display.