•SetupSequence
Setting
Display
Description
Е м
ENT
S/W Version
v1.01
S/W Version 1.01 (Note: this information only applies to versions
1.00 to 1.09)
DisplayandInputs
Input type
P=1
P=2
P=3
P=4
P=5
P=6
P=7
P=8
P=9
J Type Thermocouple
K Type Thermocouple
N Type Thermocouple
T Type Thermocouple
E type Thermocouple
B Type Thermocouple
S Type Thermocouple
R Type Thermocouple
millivolt signals (no CJC)
Next Prev Accept
Display units
dEgC
dEgF
-
Degrees Celsius
Degrees Fahrenheit
Skipped for mV inputs/display
Toggle
Accept
Display range
dHI=
870
Introduces display high value
Value, e.g., 870 °C
Toggle
Accept
dLO=
-50
Introduces display low value
Value, e.g., -50 °C
Toggle
Accept
Input range
InL=
0
Input range lower limit in display units
e.g., 0 °C
-
Dec
-
Inc
Next
Accept
InH=
650
Input range upper limit in display units
e.g., 650 °C
-
Dec
-
Inc
Next
Accept
Damping factor
dF=
2
Introduces the damping factor
Value, e.g., 2
-
Dec
-
Inc
Next
Accept
Enable/DisableAlarms
Alarms 1 & 2
Select
AL=Y
AL=n
Enable
Disable
Toggle
Accept
Note: alarm settings are only shown if they are enabled.
Alarmresetmode
Alarm reset
sequence
nOr
rES
Automatic reset
Manual reset
Toggle
Accept