Setupsequence(continued) – Weidmuller UTCAR - Universal glavanically isolated signal converter Benutzerhandbuch

Seite 25

Advertising
background image

2

Alarmchannelone

Coil energisation

A1nE

A1nd

Normally energised
Normally de-energised

Toggle

Accept

Alarm type

A1=L

A1=H

A1=0

Low type (active below setpoint)
High type (active above setpoint)
T/C Burnout alarm (the sequence skips to chan-
nel two if you select this option)

Toggle

Accept

Setpoint value

SP1=

50.0

Setpoint value
e.g., 50.00 %

-

Dec

-

Inc

Next

Accept

Deadband value

db1=

0.1

Deadband value
e.g., 0.01 %

-

Dec

-

Inc

Next

Accept

Timer delay

dL1=

20

Timer delay (set to 0s to disable)
e.g., 20 s

-

Dec

-

Inc

Next

Accept

Alarmchanneltwo

Coil energisation

A2nE

A2nd

Normally energised
Normally de-energised

Toggle

Accept

Alarm type

A2=L

A2=H

Low type (active below setpoint)
High type (active above setpoint)

Toggle

Accept

Setpoint value

SP2=

50.0

Setpoint value
e.g., 50.0 %

-

Dec

-

Inc

Next

Accept

Deadband value

db2=

10.0

Deadband value
e.g., 10.0 %

-

Dec

-

Inc

Next

Accept

Timer delay

dL2=

20

Timer delay

(set to 0 s to disable)

e.g., 20 s

-

Dec

-

Inc

Next

Accept

Setpointsecurity

Setpoint

security

SECy

SECn

Setpoints fixed at setup
Can change setpoints

Toggle

Accept

SetupSequence(continued)