Contemporary Control Systems BACnet Cube I/O BMT-AO4 Benutzerhandbuch
Seite 3

METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Deutschland
Tel. +49 7702 533-0 | Fax +49 7702 533-433
Montageanleitung siehe www.metz-connect.com
Fortsetzung Beschreibung der Software
Function Table for Analog Output
Out_Of_Service
Priority_Array
Present_Value
Analog Output
OUT_OF_SERVICE
0
NULL
Relinquish_Default
Relinquish_Default
0
Value
Value
Value
1
NULL
Relinquish_Default
unchanged
1
Value
Value
Analog Value Object 1
Property
Remark / Value
RW
Object_Identifier
analog-value, instance 1
R
Object_Type
ANALOG_VALUE (2)
R
Object_Name
max. 42 Bytes, default “Watchdog Time”
RW-E
Description
max. 84 Bytes, default “”
RW-E
Present_Value
Time Constant of Watchdog Timer,
0: Watchdog is inactive, Maximum: 655.34 seconds
RW-E
Status_Flags
IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE: 0
R
Event_State
NORMAL (0)
R
Out_Of_Service
FALSE (0)
R
Units
seconds (73)
R
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash
Der Watchdog Timer setzt Present_Value von allen Ausgangsobjekten zurück auf Relinquish_Default, wenn die BACnet Kommunikation
dauerhaft ausfällt. Der Timer wird neu gestartet, wenn eine BACnet Nachricht mit einer APDU empfangen wird.
Wenn der Timer ausläuft, werden die Prioritätsfelder alle Ausgangsobjekte komplett auf NULL gesetzt.