3001S / 3002S - 9

english

Electrical installation

The operating voltage and frequency of the power supply must correspond
with the data on the type plate of the actuator.
For versions with rated voltages of 230 V and 120 V the regulations for power
current systems must be observed. The circuit diagram for connecting the
rotary actuator is to be found in the actuator cover.

Fusing is at the mains side, the fuse values depend on the voltage.

ATTENTION!

• Do not connect both directions of rotation simultaneously!

• When changing the directions of rotation, an interval of 1

sec must be guaranteed.

NOTE

For rotary actuators with alternating current motor, each
rotary actuator must be triggered by its own switch or realy.
With direct parallel switching of serval actuators using a
common switch or relay contact, faulty currents arise which
can lead to the destruction of the actuator.

Supply voltage

Fuse protection

12 V =

6,3 A semi-slow

24V =

4,0 A semi-slow

48 V =

2,0 Asemi-slow

120 V ~

2,0 A semi-slow

230 V ~

1,0 A semi-slow