English, Technical data – Burkert Type 3002 Benutzerhandbuch

Seite 7

Advertising
background image

3001S / 3002S - 5

english

Technical data

Mechanical data

Housing material

polycarbonate

Rated load torque

Type 3001 S
Type 3002 S

50 Nm

135 Nm

Folding square

90°

Floating time [s/90°]

28 s

Shaft end

square socket

Ambient temperature

standard with auxiliary
function

-20 to +50 °C
-10 to + 50 °C

Versions

standard on

inquiry

2-position actuator
3-position actuator

Mass

Type 3001 S
Type 3002 S

ca. 3.6 kg
ca. 4.0 kg

Auxiliary functions

- torque limit
- automatic resetting with power failure

Electrical Data

Operating voltage

12, 24 V DC
120 V/50-60 Hz

230 V/50-60 Hz

Voltage tolerance

± 10 %

Capacity

AC

DC

with auxiliary functions

55 W
20 W
40 W

Type of rating

AC

UC/DC

with auxiliary functions

Intermittent operation 50% ED

Continuous operation 100% ED
Continuous operation 100% ED

Electrical connection

Device plug sockets for cable

6-7 mm or cable gland

Pg 11 according to DIN 46 32

Protection class

IP 65

Limit switch

single-pole change over switch, max. 250 V/10 A

Potentiometer

R= 1k

, max. 2 W

Standard signal input

4 to 20 mA
0 to 10 V

R

input

< 50

R

input

> 10 k

Accuracy during
standard signal control

Linearity deviation
Hysteresis

< ± 1,5 %
< ± 1,5 %

Advertising
Dieses Handbuch ist für die folgenden Produkte bezogen werden: