16 - 3001S / 3002S

english

Adjustment of the electronics

The electronics may have to be readjusted.

Give minimal control signal (0 V, 0 mA or 4 mA) and set position with
trimmer „ZERO POINT“.

Give minimal control signal (10 V or 20 mA) and set position with „ADJUST"
trimmer.

NOTE

With an input range of 4 to 20 mA the min. position is also
dependent on „ADJUST“ trimmer. You must check the zero
point setting again. With min./max. input signal a limit switch is
reached; if necessary, set this anew (see "Setting the limit
positions").

Standard signal input option

An additional module allows the direct conversion of the input signal (0-10 V or
0/4-20 mA) in a proportional position angle of the rotary actuator. The motor is
controlled electronically. Control input and power supply are separated
galvanically.

Putting into operation

Attach operating voltage and control signal according to diagram in the
cover.

Input signal

Check setting of the respective signal type on S5/S6 on the circuit board
3001-2472.1 (230V/50Hz) or 3001-3472.2 (24V/AS) and you check these.

Position 1 = 0 to 10 V
Position 2 = 0/4 to 20 mA

Direction of rotation

The correct direction of rotation of the drive should be checked by applying a
signal. If the actuator rotates in the false direction on increasing the signal
please change the working direction on S1-S4.

Position 1 = 10 V or 20 mA = „CLOSED“ (Position C),
Stellung 2 = 10 V or 20 mA = „OPEN“ (Position A).