WIKA Operating instructions pressure gauges Model 4 with 831 per ATEX

13

080

4

.03 1

/

009 GB/D/F/E

GB

Installation

In order to ensure that with both models 43X.30 and 43X.36 pressure can

be safely and reliably vented through the case back, a distance of at least

5 mm must be left free behind the case!

After installation, instruments with liquid filling must be operated in a vented

condition by turning the pressure equalising valve.

In order to avoid any additional heating, the instruments must not be exposed

to direct solar irradiation while in operation!

Admissible ambient and working temperatures

When installing the pressure gauge it has to be ensured that, taking the influ-

ence of convection and heat radiation into consideration, no upper or lower

deviation from the permissible ambient and medium temperatures can occur.

The influence of temperature on the class accuracy is to be observed.

Permissible vibration load at the mounting point

The instruments should always be installed in locations free from vibration.

If necessary, it is possible to isolate the instrument from the mounting point

by installing a flexible connection line between the measuring point and the

pressure gauge and mounting the instrument on a suitable bracket.

If this is not possible, the following limit values must not be exceeded:

Dry gauges:

Frequency range < 150 Hz

(Model 43)

Acceleration < 0.7 g (7 m/s



)

Liquid-filled gauges:

Frequency range < 150 Hz

(Model 433)

Acceleration < 4 g (40 m/s



)

The liquid filling must be checked on a regular basis.

The liquid level must not drop below 75 % of the gauge diameter.

Commissioning

During the commissioning process pressure peaks must be avoided at all costs.

Open the shut-off valves slowly.

7. Commissioning, operation