Operating instructions safety switches stp...as3, Electrical connection, Setup – EUCHNER STPxxxAS3 Benutzerhandbuch

Seite 6: As-interface status messages, Functional check, Inspection and service, Ec declaration of conformity, Technical data

Advertising
background image

Operating Instructions Safety Switches STP...AS3

EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de [email protected]

Electrical connection

For use and operation as per the requirements of

(UL), an isolating transformer or a power supply

with secondary overcurrent protection (3 A) must be
used.

The safety switch is connected to the bus system
with a 4-core connecting cable with M12 plug
connector via a passive AS-Interface distribution box
with yellow AS-Interface cable.

Figure 2: Terminal assignment M12 plug connector

f

Maximum cable lengths

The cable length decreases due to the increasing
current draw depending on the number of switches.

Number of switches Max. cable length [m] *

6

300

7

260

8

225

9

200

10

180

* Cable length between power supply unit and last switch

Setup

f

Setting the AS-Interface address

The address can be set prior to or after assembly.
The AS-Interface address of the safety switch is set
using an AS-Interface programming device. Addresses
1 to 31 are valid.
The unit is programmed by connecting the program-
ming device to the M12 plug connector on the safety
switch with an AS-Interface programming device.
The default setting for the address on delivery is 0.

f

Configuration in the AS-Interface safety monitor

(see operating instructions for the AS-Interface safety
monitor and status table)
The safety switch is configured in the AS-Interface
safety monitor with the AS-Interface address set as
follows, for example:

f

Two-channel dependent

f

Synchronization time = infinite

In this operating mode, the safety guard must be
opened each time prior to restarting in order to per-
form the start-up test.

f

Dual-channel independent
The guard locking is opened and closed using the
output D0. When the guard locking is open, the
safety circuit shuts down. It is not necessary to
open the door. Safety is provided again when the
guard locking is closed.

The dual-channel feature and the door contact are
not tested in this configuration. Additional measures
outside the monitor must be provided for testing.

For the expanded monitor SFM-B02, the following
configuration is possible:

f

Dual-channel conditionally dependent

f

Independent: In-1

The guard locking is opened and closed using the
output D0. When the guard locking is open, the safety
circuit shuts down. It is not necessary to open the
door. Safety is provided again when the guard locking
is closed.

The switch is monitored for malfunction; the door
contact (SK) must not be switched before the guard
locking contact (ÜK).

AS-Interface status messages

Color

State

Explanation

LED

green illuminated Normal operation

red

illuminated No data exchange between

green illuminated master and slave.

Cause:
- Master in STOP mode
- Slave not in LASP
- Slave with wrong IO/ID
- Reset on slave active

red

illuminated No data exchange between

green

flashing

master and slave.
Cause: Slave address = 0

red

flashing

Device fault in the slave.

green

flashing

Please contact

red

flashing

EUCHNER.

green illuminated

Two additional function LEDs may be activated via
the AS-Interface bus, e.g. to display the door status.
The red LED is switched as an output on the AS-
Inteface bus via bit D1 and the green LED via bit D2.

Functional check

Warning! Danger of fatal injury as a result of faults
in installation and functional check.
Before carrying out the functional check, make
sure that there are no persons in the danger
area. Observe the valid accident prevention
regulations.

After installation and any fault, the safety function must
be fully checked. Proceed as follows:

f

Mechanical function test

The actuator must slide easily into the actuating head.
Close the safety guard several times to check the
function.

f

Electrical function test

1. Switch on operating voltage.
2. Close all safety guards.

Guard locking by solenoid force

¨

Activate

guard locking.

f

The machine must not start automatically.

f

It must not be possible to open the safety guard.

3. Enable operation in the control system.

f

It must not be possible to deactivate the guard
locking as long as operation is enabled.

4. Disable operation in the control system and

deactivate guard locking.

f

The safety guard must remain locked until there is
no longer any risk of injury.

f

It must not be possible to start the machine as long
as the guard locking is deactivated.

Repeat steps 2 - 4 for each safety guard.

Inspection and service

If damage or wear is found, the complete switch
and actuator assembly must be replaced.
Replacement of individual parts or assemblies,
especially of the actuating head, is not permitted!

Note: The year of manufacture can be seen in the
bottom, right corner of the rating plate.
No servicing is required, but regular inspection of
the following is necessary to ensure trouble-free long-
term operation:

f

correct switching function

f

secure mounting of components

f

dirt and wear

f

loose plug connectors.

Exclusion of liability under the following
circumstances

f

incorrect use

f

non-compliance with safety regulations

f

installation and electrical connection not performed
by authorized personnel

f

failure to perform functional checks.

EC declaration of conformity

The manufacturer named below herewith declares that
the product fulfills the provisions of the directive(s)
listed below and that the related standards have been
applied.
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen, Germany
Directives applied:

f

Machinery directive 2006/42/EC

Standards applied:

f

EN 60947-5-1:2004 + Cor.:2005 + A1:2009

f

EN 1088:1995+A2:2008

Leinfelden, July 2010
Dipl.-Ing. Michael Euchner
Director
Duc Binh Nguyen
Authorized representative empowered to draw up
documentation
The signed EC declaration of conformity is included
with the product.

Technical data

Parameters

Value

Housing material

Reinforced
thermoplastic

Deg. of prot. acc. to IEC 529 IP 67, mating connector plugged
Mechanical life

1x10

6

operating cycles

Ambient temperature

-20 ... +55°C

Installation position

Any

Approach speed, max.

20 m/min

Actuating force

35 N

Extraction force

30 N (not locked)

Retention force

20 N

Locking force F

max

2,500 N

Locking force F

Zh

acc. to

GS-ET-19
Weight

Approx. 0.5 kg

Switching principle SK, ÜK

Positively driven, slow-action
switching contact

EMC protection requirements Acc. to EN 50295 (AS-Interface

standard) and IEC 62026

Minimum travel and overtravel
Approach direction

Actuator

S

Actuator

L for

Standard

Insertion funnel

horizontal (h) + vertical (v)

24.5 + 5

28.5 + 5

AS-Interface data acc. to

EA code: 7

AS-Interface specification 3.2 ID code: B
Operating voltage AS-Interface DC 22.5 ... 31.6 V
Total current consumption, max. 400 mA
Valid AS-Interface addresses

1 - 31

AS-Interface inputs

In accordance with AS-Interface
Safety at Work

Door monitoring contact SK

D0, D1

Solenoid monitoring contact ÜK D2, D3
AS-Interface outputs
D0

Guard locking solenoid,
1 = solenoid energized

D1

Red LED, 1 = LED on

D2

Green LED, 1 = LED on

Reliability values according to EN ISO 13849-1
B

10d

5 x 10

6

Subject to technical modifications; no r

esponsibility is accepted for the accuracy of this information. © EUCHNER GmbH + Co. KG

106656-03-10/11 (translation of the original operating instructions)

1

AS-Interface +

2

Not used

3

AS-Interface -

4

Not used

View of safety switch

plug connector

4

3

1

2

(F

Zh

=

F

max

) = 2000 N

1,3