7 setup interface and fine calibration, Setup interface, Fine calibration – JUMO 707010 dTRANS T01 Ex - 2-Wire Transmitter Operating Manual Benutzerhandbuch
Seite 37

13
7 Setup interface and fine calibration
Setup interface
The setup interface is available for configuring the transmitter from
a PC. The connection is via the PC interface with a TTL/RS232 con-
verter and adapter.
The cover flap must be closed after programming.
Configurable parameters:
- tag number (10 characters)
- sensor type
- connection circuit (2-/3-/4-wire)
- external or internal cold junction
- custom linearization
- range limits
- output signal rising/falling (inversion)
- digital filter
- response to probe break/short-circuit
- recalibration (fine calibration)
- lead resistance for 2-wire circuit
If no Ex supply unit (supply isolator) is available, the 2-wire transmit-
ter can also be configured using a 9V block battery.
Fine calibration
Fine calibration means adjustment of the output signal. The signal
can be adjusted within ± 5% of the 20mA end value. Fine calibra-
tion is performed using the setup program. Values for 4 mA (zero
point), 20 mA (full scale) and offset can be calibrated separately, us-
ing the setup program.