For review mode, press the
Å
and
ì
keys simultaneously.
Press the
Å
and
ì
keys to move through the setup sequence (see
table). Greyed items in the setup table are not shown in review mode.
A 10s timeout applies for review mode or you can press to quit.
Note: You can use review mode while the instrument is in service and
the analogue output and alarms will continue to operate correctly.
Clearingtrippedalarms
You can acknowledge a tripped alarm by simply pressing the key for
that channel (ï for Alarm 1 or ENT for Alarm 2).
Displayingthealarmsetpoints
To check a setpoint, simply press the key for that channel (ï for Alarm 1
or ENT for Alarm 2). If the alarms are disabled the display will show ---- .
Adjustingthealarmsetpoints
To change a setpoint, hold down the key for that channel (ï for Alarm
1 or ENT for Alarm 2). You will then be able to change the value using
the arrows. Release the key to save the value. Note: There are limits
for the setpoint values that depend on the input range setting and you
cannot change the value if setpoint security is on.
Installation
These units must only be installed by qualified staff in accordance with
the information given in this manual and all relevant national electrical
wiring and safety rules must be followed.
Locate the instrument in an area that is free from dust, moisture and
corrosive gases.