Setupsequence – Weidmuller CLCAR - Universal galvanically isolated signal converter Benutzerhandbuch
Seite 24

2
•SetupSequence
Setting
Display
Description
Е м
ENT
S/W Version
1.21
S/W Version 1.21 (Note: this information only applies to versions
1.20 to 1.29)
DisplayandInputs
Input type
P=1
P=E
Current (mA)
Voltage (V)
Toggle
Accept
Input range
IPL=
4.00
Input range lower limit
e.g., 4.00 mA
-
Dec
-
Inc
Next
Accept
PH=
20.00
Input range upper limit
e.g., 20.00 mA
-
Dec
-
Inc
Next
Accept
Input
Calibration?
C Pn
C Py
Skip input calibration
Calibrate the inputs
Toggle
Accept
Damping factor
dF=
2
Introduces the damping factor
Value, e.g., 2
-
Dec
-
Inc
Next
Accept
Curve security
CUSy
CUSn
Curve parameters locked
Curve parameters accessable
Toggle
Accept
Display decimal
point
dP=
.
Decimal point position
-
Shift
Next
Accept
Number of
breakpoints
nP=
21
Introduces number of breakpoints
Value, e.g., 21
-
Dec
-
Inc
Next
Accept
Breakpoint
distribution
HEuN
YEun
Hyod
Fixed input interval (H-Even)
Fixed output interval (Y-Even)
Variable interval (H/y-odd)
Toggle
Accept
Display Range
yLO=
0.0
Display range lower limit
e.g., 0.0
-
Dec
-
Inc
Next
Accept
yHI=
100.0
Display range Upper limit
e.g., 100.0
-
Dec
-
Inc
Next
Accept
Breakpoints
H1=
0.0
y1=
4.0
...
H101
100.0
Y101
20.0
Introduces breakpoint 1 H-value,
e.g., 0.0 %
Introduces breakpoint 1 y-value,
e.g., 4.0
...
Introduces breakpoint 101 H-value,
e.g., 100.0 %
Introduces breakpoint 101 Y-value,
e.g., 20.0
-
Dec
-
Dec
-
Dec
-
Dec
-
Inc
-
Inc
-
Inc
-
Inc
Next
Accept
Next
Accept
Next
Accept
Next
Accept
Note: ï button shows identifier when number is on display or skips to end when identifier is on display