•Calibration

General
The CLC/AR is factory calibrated and should not require adjustment
until the next scheduled calibration. However, if you require a different
input or output range to the one ordered, you will have to recalibrate
the instrument.
Allow the instrument 15 minutes of powered operation (to reach a
stable temperature) before you start the calibration.
During calibration allow a few seconds for signals to stabilise before
accepting the value.

Equipmentrequirements
• A suitable current/voltage source (must be able to generate mA and

voltage signals to ±0.05 % or better accuracy)

• An accurate digital multimeter (accurate to 0.05 mV and ±0.1 μA)

TerminalConnectionsforinputcalibration

CalibrationStage

Signaltype

Terminal

Current (mA) inputs

Milliamp source +

2

Milliamp source −

3

Voltage (V) inputs

Voltage source +

4

Voltage source −

3