1

Connections
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
Strip wires to  mm from the ends. Use a suitable ferrule for multi-
stranded wires (do not solder). Use 12-28 AWG Cu Wire rated for
temperatures above 0 °C Only, tighten to .5 lb-In.

Terminal

Signal

1

24 V DC (out)

Input signals

2

Current +

3

Common −

4

Voltage +

5

Not used

6

7

Link to change the set-up

Security Link

8

9

Neutral −

Power supply

10

Live +

11

Channel one

Alarm outputs

12

Channel two

13

Common

14

Output +

Analogue outputs

15

Current −

16

Voltage −

Case

Earthing is via a stud on lower side of case