Setupsequence – Weidmuller CNDR - Universal galvanically isolated signal converter Benutzerhandbuch
Seite 20

20
•SetupSequence
Setting
Display
Description
Е м
ENT
S/W Version
1.10
S/W Version 1.10
(Note: this information only applies to versions 1.10
to 1.19)
DisplayandInputs
Conductance
range
rng=
0.20
1.00
5.00
20.00
Introduces the setting
200 µS range
1 mS range
5 mS range
20 mS range
Toggle
Accept
Input range
(for analogue
output)
InL=
0.00
Input level for analogue output low
e.g., 0.00 mS
-
Dec
-
Inc
Next
Accept
InH=
10.00
Input level for analogue output high
e.g., 10.00 mS
-
Dec
-
Inc
Next
Accept
Damping factor
dF=
2
Introduces the damping factor
Value, e.g., 2
-
Dec
-
Inc
Next
Accept
Probe factor
pF=
1.00
Introduces the probe factor
Value, e.g., 1.00
-
Dec
-
Inc
Next
Accept
Temperaturecompensation
Compensate for
temperature?
Cenb
Cdsd
Enable
Disable
Toggle
Accept
Number of
breakpoints
nP=
4
Introduces number of linearisation points
Value, e.g., 4
-
Dec
-
Inc
Next
Accept
Breakpoints
H1=
0.0
r1=
0.80
...
H4=
100.0
r4=
20.0
Introduces breakpoint 1 temperature (°C),
e.g., 0.0 °C
Introduces breakpoint 1 ratio,
e.g., 0.80
...
Introduces last breakpoint temperature (°C)
e.g., 100.0 °C
Introduces breakpoint 4 ratio,
e.g., 20.0
-
Dec
-
Dec
-
Dec
-
Dec
-
Inc
-
Inc
-
Inc
-
Inc
Next
Accept
Next
Accept
Next
Accept
Next
Accept
Note: you must at least one ratio of 1.00
(for the reference temperature) or Err will be displayed
Alarmchannelone
Coil energisation
A1nE
A1nd
Normally energised
Normally de-energised
Toggle
Accept
Alarm type
A1=L
A1=H
Low type (active below setpoint)
High type (active above setpoint)
Toggle
Accept