1

Inputsignaltypeandrange

You can not change the input type during set-up mode. The input is

either current or voltage according to the components used when the
unit was built.

The input range is determined by the values supplied during

calibration. So, if you change the range displayed in setup, you will
have to calibrate the inputs.

DampingFactor

The PTX800A uses digital filtering to smooth the input signal. The

damping factor sets the amount of filtering from minimum damping
(factor of one) to the maximum (factor of ninety nine).

TransferFunction

To use the PTX800A with square law rate measuring devices, like

differential pressure cells, set the transfer function to square law.
Otherwise use a linear setting. For more complex relationships
between rate and signal level you can use a CLC/AR to linearise your
input signal.

Lowcut-outrate

To prevent accumulated errors at low input levels, you can set a low

cut-out rate. When the input is below this value the total does not
increase.

Totaldecimalpoint

The total decimal point position sets the number of decimal places for

the total display. Totals are displayed using the full eight digits.

Ratedecimalpoint

Sets the number of decimal places for the rate display. Rates are

displayed as five digit numbers.