Inputcalibration, 41 procedure, Terminal connections for input calibration are – Weidmuller PTX800A - Configurable counter and totalizer Benutzerhandbuch
Seite 41

41
Procedure
Whenthe
displayshows
Action/Description
Put the instrument in setup mode and scroll through the main menu
CALOut_n
Press ì or Å
CAlOut_y
Press
PGM to select output calibration
Out_LO_=
Connect the multimeter to measure the output level, then press
PGM
4.00
Press
PGM
Measure the output signal
Adjust the output (using the ì or Å keys) until the output is at the value shown
When you are happy that the output is correct, press
PGM
Out_HI_=
Press
PGM
20.00
Press
PGM
Measure the output signal
Adjust the output (using the ì or Å keys) until the output is at the value shown
When you are happy that the output is correct, press
PGM
Save
Continue with the setup sequence.
Note: Do not remove the power while the save message is on display.
InputCalibration
Terminal Connections for Input calibration are:
CalibrationStage
Signaltype
Terminal
mA/Voltage Signal Source
Signal +
11
Signal –
10