Setupsequence(continued) – Weidmuller PTX800A - Configurable counter and totalizer Benutzerhandbuch
Seite 35

5
Totalandratedisplaysettingsandscaling
Rate decimal
point
tot_dp=
12.345
Introduces rate decimal point
Demo, e.g., rate shown to 3 decimal places
-
Shift
-
Shift
Next
Accept
Rate timebase
rate_SEC
rate_min
rate_Hr
rATe_day
Rate is in units per second
Rate is in units per minute
Rate is in units per hour
Toggle
Accept
Rate Range
rAtELO=
0.00
Introduces rate low value
Value, e.g., 0.00 %
-
Dec
-
Inc
Next
Accept
rAtEHI=
100.00
Introduces Input high value
Value, e.g., 100.00 %
-
Dec
-
Inc
Next
Accept
Cut-out rate
rateCut=
1.00
Introduces the low cut-out rate
Value, e.g., 1.00 %
-
Dec
-
Inc
Next
Accept
Show rate or
total
dis=rate
dis=tot
Display normally shows the rate
Display normally shows the total
Toggle
Accept
Total decimal
point
tot_dp=
1234.5
Introduces total decimal point
Demo, e.g., total shown to one decimal place
-
Shift
-
Shift
Next
Accept
Total scaling
factor
tot_sf=
1
Introduces total scaling factor
Value, e.g.,total units = rate units
-
x0.1
-
x10
Next
Accept
Resetkeyenable
Reset Total Key
Enable
En_resY
En_resn
RESET key resets count
RESET key ignored
Toggle
Accept
Alarmenable
Alarms 1 & 2
Select
AL=Yes
AL=NO
Enable
Disable (Select this option for PMX420)
Toggle
Accept
Alarmchannelonesettings
Coil energisa-
tion
A1_nor_E
A1_nor_d
Normally energised
Normally de-energised
Toggle
Accept
Alarm one type
A1=_rate
A1=_tot_
Channel one monitors rate
Channel one monitors total
Toggle
Accept
Alarm one
action
A1=_LO
A1=_HI
Low type (active below setpoint)
High type (active above setpoint)
Toggle
Accept
Setpoint value
Set_Pt1=
50.00
Setpoint value
e.g., 50.00 %
-
Dec
-
Inc
Next
Accept
Deadband
value
dband_1=
0.01
Deadband value
e.g., 0.01 %
-
Dec
-
Inc
Next
Accept
Timer delay
delay_1=
20
Timer delay (set to 0 s to disable)
e.g., 20 s
-
Dec
-
Inc
Next
Accept
SetupSequence(continued)